주요특징
- 다양한 산업용 프로토콜 (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU) 제공
- 90종 이상 다양한 IO 모듈 구성 및 제공 (유니버셜 타입의 디지털 입력 모듈, 국내 최초 32 Points 슬라이스 I/O 모듈 , ERNI타입 커넥터 입출력 모듈)
- 컴팩트한 사이즈와 슬라이스 모듈 확장 방식으로 효율적인 공간 활용
- 사용자 편의를 고려한 Removable Terminal Block 방식 제공으로 전장 배선 및 설치 시 작업자에 쉽고 편리한 작업 환경 제공
| Interface Specification, GL-9089 (MODBUS TCP/UDP NETWORK ADAPTER) | |
| Adapter Type | Slave node (MODBUS/TCP,MODBUS/UDP Server) | 
| Protocol | MODBUS/TCP,MODBUS/UDP,HTTP,DHCP,10 TCP Connections | 
| Sub-Protocol | **Ethernet/IP | 
| Max. Expantsion Module | 16 slots | 
| Max. Input / Output Data Size | Max. Input 256 bytes / Output 256 bytes | 
| Max Length Bus Line | Up to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP | 
| Max. Nodes | Limited by Ethernet Specification. | 
| Baud Rate | 100Mbps, Auto-negotiation, Full duplex | 
| Interface Connector | RJ-45 socket * 2pcs | 
| IP-Address Setup | Via DHCP/BOOTP or IOGuide(Crevis Software) | 
| IP-Address Range | xxx.xxx.xxx.1 ~ 253 (User area)xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function) | 
| IAP Mode | When DIP Switch 1 to 8 setting is 254 or 255(Using only Internet Explorer / recommended version 11) | 
| Indicator | 4 LEDs 1 Green/Red, Module Status (MOD) 1 Green, Physical Connection (LINK) 1 Green, Exchange Data/Traffic Present (ACTIVE) 1 Green/Red, Expansion I/O Module Statsus (IOS) 2 LEDs (each RJ45 Connector) 1 Yellow, Link/Active1 Green, Not used | 
| Module Location | Starter module left side of G-Series system | 
| General Specification | |
| UL System Power | Supply voltage : 24Vdc nominal, Class2 | 
| System Power | Supply voltage : 24Vdc nominal Supply voltage range : 15~28.8VdcProtection : Reverse polarity protection | 
| Power Dissipation | 75mA typical @ 24Vdc | 
| Current for I/O Module | 1.0A @ 5Vdc | 
| Isolation | System power to internal logic : Non-isolation | 
| UL Field Power | Supply voltage : 24Vdc nominal, Class2 | 
| Field Power | Supply voltage : 24Vdc typical (Max. 30Vdc) * Field Power Range is different depending on IO Module series.Refer to IO Module`s Specification. | 
| Max. Current Field Power Contact | DC 8A Max | 
| Wiring | I/O Cable Max. 2.0㎟(AWG 14) | 
| Torque | 0.8Nm(7 lb-in) | 
| Weight | 76g | 
| Module Size | 22mm x 109mm x 70mm | 
| Environment Condition | Refer to ‘1. Environment Specification’ | 
| Pin No | Signal Description | 
| 1 | System Power, 24V | 
| 2 | System Power, Ground | 
| 3 | F.G | 
| 4 | Field Power, Ground | 
| 5 | Field Power, 24V | 