crevis

GL-9084

CC-Link IE Field Basic Network Adapter


제품비교 담기

도움이 필요하세요?

샘플요청 견적문의
썸네일이미지 원본

주요특징


- 다양한 산업용 프로토콜 (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU) 제공

- 90종 이상 다양한 IO 모듈 구성 및 제공 (유니버셜 타입의 디지털 입력 모듈, 국내 최초 32 Points 슬라이스 I/O 모듈 , ERNI타입 커넥터 입출력 모듈)

- 컴팩트한 사이즈와 슬라이스 모듈 확장 방식으로 효율적인 공간 활용

- 사용자 편의를 고려한 Removable Terminal Block 방식 제공으로 전장 배선 및 설치 시 작업자에 쉽고 편리한 작업 환경 제공
Interface Specification, GL-9284 (MODBUS TCP/UDP NETWORK ADAPTER)

Adapter Type

Slave station (CC-Link IE Field Basic Server)
Protocol CC-Link IE Field Basic, SLMP
Sub-Protocol MODBUS/TCP,MODBUS/UDP,HTTP,DHCP,10 TCP Connections
Port number

61450 (CyclicData)

61451 (port number of the slave station of NodeSerch)
Max. Expantsion Module 16 slots
Number of occupied stations 1 ~ 4 stations
Max. Data Size(RX, RY) each 32 bytes (4 Stations occupied)
Max. Data Size(RWr, RWw) each 256 bytes (4 Stations occupied)
Max. Input / Output Data Size Max. Input 256 bytes / Output 256 bytes
Max. link points per station (RX, RY) each 64 points

Max. link points per station
(RWr, RWw)

each 32 points
Max Length Bus Line Up to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Max. Nodes

64 node

Baud Rate 10/100Mbps, Auto-negotiation, Full duplex
Interface Connector RJ-45 socket * 2pcs
IP-Address Setup Via DHCP/BOOTP or IOGuide(Crevis Software)
IP-Address Range

xxx.xxx.xxx.1 ~ 253 (User area)

xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function)
IAP Mode

When DIP Switch 1 to 8 setting is 254 or 255

(Using only Internet Explorer / recommended version 11)
Indicator

4 LEDs

1 Green/Red, Module Status (MOD)

1 Green, Physical Connection (NET)

1 Green, Exchange Data/Traffic Present (ERR)

1 Green/Red, Expansion I/O Module Statsus (IOS)

2 LEDs (each RJ45 Connector)

1 Yellow, Link/Active

1 Green, Not used
Module Location Starter module left side of G-Series system
General Specification
UL System Power Supply voltage : 24Vdc nominal, Class2
System Power

Supply voltage : 24Vdc nominal

Supply voltage range : 15~28.8Vdc

Reverse polarity protection
Power Dissipation 60mA typical @ 24Vdc
Current for I/O Module 1.0A @ 5Vdc
Isolation

System power to internal logic : Non-isolation
System power I/O driver : Isolation

UL Field Power Supply voltage : 24Vdc nominal, Class2
Field Power

Supply voltage : 24Vdc typical (Max. 30Vdc)

* Field Power Range is different depending on IO Module series.

Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 8A Max
Wiring I/O Cable Max. 2.0㎟(AWG 14)
Torque 0.8Nm(7 lb-in)
Weight 76g
Module Size

22mm x 109mm x 70mm

Environment Condition Refer to ‘1. Environment Specification’
Pin No Signal Description
1 System Power, 24V
2

System Power, Ground

3 F.G
4 Field Power, Ground
5

Field Power, 24V